LABORATORY SPECIFICATIONS (PER HALF-FLOOR SPACE)
-
ELECTRIC SERVICE
208/120V power provided to electrical closets on each floor, conduit runs from electrical closet to panel in Tenant suite. Lab electric capacity = 7.5 watts per usable SF of lab area.
-
BACK-UP POWER CAPACITY
2.5 watts per useable SF of lab area; connected to 350 kW/480v diesel emergency generator.
-
PLUMBING
Tempered water for emergency shower and eye wash station. Building managed pH-neutralizing system.
-
HVAC
Labs designed with central air handling HVAC system providing 100% non-circulated air at 1.25 cfm per usable lab SF (8 ACH). Humidity designed for no more than 60% RH. N+1 redundancy for exhaust fan, pumping, and boilers.
-
CEILING HEIGHTS / FLOOR LOAD
Deck-to-deck: 11’-6” / Deck-to-grid: 8’-6”
Floor load suitable for typical lab use. -
BUILDING ELEVATORS
One (1) 3,500 lb. capacity freight elevator, 250 f.p.m. (entry door: 3’-4”/ cab size: 4’-10” x 6’-8” x 7’-11”). Two (2) 2,500 lb. capacity passenger elevators, 250 f.p.m.