LABORATORY SPECIFICATIONS (PER HALF-FLOOR SPACE)

  • ELECTRIC SERVICE

    208/120V power provided to electrical closets on each floor, conduit runs from electrical closet to panel in Tenant suite. Lab electric capacity = 7.5 watts per usable SF of lab area.

  • BACK-UP POWER CAPACITY

    2.5 watts per useable SF of lab area; connected to 350 kW/480v diesel emergency generator.

  • PLUMBING

    Tempered water for emergency shower and eye wash station. Building managed pH-neutralizing system.

  • HVAC

    Labs designed with central air handling HVAC system providing 100% non-circulated air at 1.25 cfm per usable lab SF (8 ACH). Humidity designed for no more than 60% RH. N+1 redundancy for exhaust fan, pumping, and boilers.

  • CEILING HEIGHTS / FLOOR LOAD

    Deck-to-deck: 11’-6” / Deck-to-grid: 8’-6”
    Floor load suitable for typical lab use.

  • BUILDING ELEVATORS

    One (1) 3,500 lb. capacity freight elevator, 250 f.p.m. (entry door: 3’-4”/ cab size: 4’-10” x 6’-8” x 7’-11”). Two (2) 2,500 lb. capacity passenger elevators, 250 f.p.m.

 TENANT SPECIFIED IMPROVEMENTS INCLUDE BENCHING, CHEMICAL FUME HOODS AND EXTRACTION DEVICES